EQUIPMENT CONNECTOR
CONNECTION BOX
BACKSHELL
NOTES:
2
2 1. THIS METHOD OF CABLE SHIELDING APPLIES TO NEW CABLE
1 INSTALLATIONS AND TO EXISTING CABLE INSTALLATION WHERE THE CABLE CAN BE REMOVED FROM THE TERMINATING EQUIPMENT
1 AND HANGERS, AND ROUTED THROUGH THE CONDUIT. INSTALLATION OF CONDUIT AND FITTINGS IN ACCORDANCE WITH THIS FIGURE
WILL PREVENT CABLE-PENETRATION EMI.
CONDUIT TERMINATION TO CONNECTION BOXED
CONDUIT TERMINATION TO ELECTRICAL/ELECTRONIC
1
CONNECTORS
2
2. SELECT CONDUIT SIZE TO ACCOMODATE CABLE OVERALL DIAMETER.
3. THE MINIMUM BEND RADIUS OF CONDUIT SHALL NOT BE EXCEEDED.
4. ELBOW FITTINGS, 45 OR 90 DEGREE, SHALL BE USED, WHERE NEEDED, TO REDUCE STRAIN ON CONNECTORS AND CONDUIT. SELECT CONDUIT FITTINGS TO MATCH CONDUIT SIZE AND TERMINATING EQUIPMENT.
5. CONDUIT FITTINGS SHALL BE SELECTED TO AVOID DISSIMILAR METALS. ANTISEIZE COMPOUND SHALL BE USED AT ALL METAL- TO-METAL JUNCTIONS AND ALL TOPSIDE JUNCTIONS SHALL BE
WEATHERPROOFED.
CONDUIT TERMINATION TO SWAGE/STUFFING TUBES
FIGURE 6. Cable shielding method, flexible metal conduit.